FrançaisEspañolPortugueseDeutschItaliano
English
Imprint and Privacy
Facebook
LinkedIn
YouTube
Instagram
    • LORENTZ S
    • Sizing
    • Download
    • Where to buy
    • Help

LORENTZ S

Help

help home

back

S1-200 systems - Connecting PV modules in series and parallel

Understanding PV module series and parallel connections for the S1-200 system

Correctly connecting PV modules in series and parallel for the S1-200 system is essential not only to ensure proper installation and optimal pump performance but also to prevent damage to the controller.

Before explaining how to make series and parallel connections, here’s a quick and easy way to make sure you don’t exceed the controller’s maximum voltage rating:

Identify the Voc (open circuit voltage) of your PV module:

You’ll find this value on the label of the solar panel. Example:

For the S1-200 system, let’s use a 100 W PV module. On the label, the Voc is listed as 23 V. (See the picture below)

fullscreen

Check the maximum voltage allowed by the S1-200 controller:

The maximum voltage is55V.

Read more information here:

  • Required solar power input

Add the Voc values of the PV modules you intend to connect in series:

Make sure the total does not exceed 55 V.

For example, in an S1-200 system, using two (2) 100 W PV modules (same as the above label), we have:

fullscreen

Important: In this example, you must not connect more than two (2) PV modules in series. Doing so would exceed the controller's voltage limit and may result in permanent damage to the S1-200 controller.

Connecting PV Modules in series

By connecting PV modules in series, you increase the total voltage of your PV system while the current remains the same.

To make the series connection, connect the positive (male) cable of one PV module to the negative (female) cable of the next module (as shown in the image below). Be careful not to exceed the maximum input voltage allowed by the controller (refer to the three steps outlined at the beginning of this article). Exceeding the controller’s voltage limit may result in permanent damage.

In this example, we use two (2) PV modules of 100 W each. Because they are connected in series, their voltages are added together, while the current stays constant.

fullscreen

For more information on how to connect two (2) 100 W PV modules (200 W), click on the following link:

  • S1-200 Systems - Connecting two 100 W PV modules in series

Connecting PV Modules in parallel

When PV modules are connected in parallel, the current (amperage) increases while the voltage remains constant.

This type of connection requires a pair of additional accessories known as Y-connectors, one for the positive connectors and one for the negative connectors (as shown in the picture below). These are necessary when connecting modules in parallel.

fullscreen

Connecting 4 x 100 W (400 W) PV modules in series and parallel

To connect four 100 W modules, start by connecting two of them in series, and then connect the other two in series as well. This configuration increases voltage within each pair while keeping current constant.

Important: You must not connect more than two 100 W modules in series. Doing so would exceed the S1-200's maximum input voltage of 55 V and could damage the controller.

Once you have two pairs connected in series, you can connect both pairs in parallel using two Y-connectors. This step increases the total current while maintaining a safe voltage, ensuring no damage to the controller.

Steps:

  1. Connect the positive (male) wire of one 100 W module to the negative (female) wire of another 100 W module (series connection).
  2. Repeat the same with the remaining two modules.
  3. Connect the two positive wires from each series pair to one Y-connector,
  4. Connect the two negative wires from each series pair to the second Y-connector,
  5. Connect the outputs of the Y-connectors to the MC4 adapter included with the S1-200 system (this is known as parallel connection),
  6. Finally, connect the remaining cable to the S1-200 controller.
fullscreen

Connecting 2 x 330 W (660 W) PV modules in parallel

In this example, we connect two 330 W PV modules directly in parallel to the S1-200 controller. These modules must not be connected in series*.

* Important: The Voc of a 330 W module is typically around 45.6 V. Connecting two in series would result in over 91 V, which exceeds the S1-200’s maximum voltage limit of 55 V and would damage the controller.

  1. Connect the positive (male) wires of both modules to one Y-connector,
  2. Connect the negative (female) wires to the other Y-connector,
  3. Connect the MC4 adapter (included in the S1-200 system box) to the outputs of the Y-connectors.
  4. Plug the final cable into the S1-200 controller.
fullscreen

Was this article helpful?

yes

no

Thanks for your feedback!

We are sorry to hear that.

send

Do you want to contact our support team about your issue?

yes

no

help home

back

quality, efficiency and simplicity

solar water pumping from the global market leaders, available for everyone

Contact

LORENTZ

Siebenstücken 24
24558 Henstedt-Ulzburg
Germany

Contact
+49 – 4193 8806 – 700

Contact

Imprint and privacy

Whistleblowing

Search

Get Social

Facebook
LinkedIn
YouTube
Instagram
© 2023 LORENTZ. All rights reserved.